Abstract
The ability to predict ferroresonance significantly relies on the accuracy of the transformer model and the power system's parameters. The accomplishment of a suitable simulation model allows the sensitivity studies to be performed to determine the degree of influence of various components and parameters of the ferroresonance phenomenon such as line length, point-on-wave switching and transformer core loss. The modelling work carried out in ATP (commercially available software) on a 1000 MVA 400/275/13 kV power transformer model is described and the simulation with field ferroresonance test recordings is verified. The maps that define the boundaries between safe and ferroresonant (fundamental, subharmonic, chaotic) regions as a function of system parameters are created through the sensitivity studies performed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.