Abstract To improve the damping of a multimachine power system, a static VAR compensator (SVC) equipped with a supplementary feedback controller is proposed. In the design of the supplementary feedback controller, a fixed‐gain proportional‐integral (PI) controller is first investigated. To further improve system dynamic performance, two types of adaptive controllers, i.e., pole‐shifting self‐tuning controllers and self‐tuning PID controllers are developed. The effectiveness of the presented adaptive control schemes is demonstrated by time domain simulation of the multimachine system subject to a three‐phase fault. It is found that both self‐tuning controllers can yield much better dynamic responses than the fixed‐gain feedback controllers under disturbance conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.