This paper presents a self-consistent multi-arcs dynamic model for high voltage polluted insulator under impulse voltage. This model is an improvement of that one developed for single arc; it is based on an electrical equivalent circuit consisting of a series of different partial arcs and residual layer resistance. It takes into account the configuration of insulator, applied voltage polarity and the instantaneous changes of discharges parameters. The proposed model enables to compute the flashover voltage and leakage current and to show the influence of dry bands on the voltage distribution along the surface and furthermore on the electrical performance of polluted insulator. It is validated using a simple plane model in the case of uniform and non-uniform polluted bands. The computed flashover voltage and leakage current are found in good agreement with those measured experimentally.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.