Abstract
This paper presents information on the selection and performance of anchors for guyed EHV transmission towers. The information used was obtained during the design and construction of two transmission lines each over 540 miles (>869 km) long in British Columbia.Five anchors have been designed and tested: (1) buried plate with compacted backfill; (2) buried steel mat or grillage with loose backfill; (3) cast-in-place concrete with loose backfill; (4) power installed helical; and (5) grouted rod anchors.The highly variable soil and access conditions along the line necessitated an anchor that could economically be installed in nearly all soil types and by ordinary construction equipment that could easily move between tower sites in rugged terrain.The simply installed, conservatively designed, cast-in-place concrete anchor was found to satisfy these requirements at reasonable cost. Power-installed helical anchors and grouted rod anchors may provide an economical anchor in more uniform soil conditions and where easier access conditions exist. However, these anchors require more detailed soil exploration and contract inspection than the cast-in-place concrete anchors.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.