Abstract

This paper describes the performance of a series of single‐story masonry houses observed during a shaking table test program carried out at the University of California Earthquake Engineering Research Center (EERC), under the sponsorship of the U.S. Department of Housing and Urban Development (HUD). The design of the test structures and the conduct of the tests on the earthquake simulator are described in a companion paper. In evaluating the observed performance, the intensity of the test motions was characterized by the measured effective peak acceleration (EPA) so that they could be related to Uniform Building Code seismic zone 2. Based on the observed behavior, it is recommended that zone 2 be divided into subzone 2A for EPA values up to 0.1 g and subzone 2B for values between 0.1 g and 0.2 g. The observed results demonstrate that masonry houses without reinforcement may be permitted in both parts of zone 2 provided that the design guidelines recommended for each subzone are followed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.