Abstract

The seismic sensors used for automatic seismic trip systems (ASTS) of nuclear power plants (NPPs) are mainly arranged on the raft foundation of reactor buildings; however, the arrangement principle of seismic sensors is not clear. In order to analyze the seismic response sensitivity of the raft foundation of reactor building in NPPs, this paper carried out the seismic response sensitivity research at seven positions on the raft foundation of a reactor building under three site conditions, with two sets of time histories as input. The results show that (1) the peak acceleration of the outer ring point of the raft foundation was the largest, and the peak acceleration of the center point was the smallest; (2) the peak value of the floor response spectrum at the outer ring point of the raft foundation was the largest, and the peak value at the center point was the smallest. In an earthquake, the outer ring point of the raft foundation of the reactor building was the most sensitive. It was suggested that the seismic sensors used for ASTS should be arranged at the outer ring of the raft foundation NPP reactor building, and the shutdown threshold shall be calculated according to site conditions and structural characteristics.