Abstract
An electrical substation consists of a complex set of equipment items that are interconnected through conductor buses or cables. If the connections are not sufficiently flexible, significant dynamic interaction may occur between the connected equipment items during a seismic excitation. This interaction is believed to be responsible for some of the observed substation equipment damage in recent earthquakes. This paper investigates the interaction between two equipment items connected by a linear spring-dashpot or spring-dashpot-mass element representing a conductor bus. It is found that the interaction between the two equipment items may significantly amplify the response of the higher-frequency equipment item. The influences of various key parameters on the interaction effect are quantified. Means for reducing the adverse interaction effect are described. Copyright © 2001 John Wiley & Sons, Ltd.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.