Abstract

The seismic performance of electrical equipment in substations has a great impact on the normal operation of the whole substation. The results of the modal analysis show that the fundamental frequency of the three devices is in the range of 0.9Hz∼1.1Hz. The maximum stress of the casing for the three devices is respectively 55.43MPa, 45.39MPa, 35.26MPa, when the peak acceleration 0.4g seismic action is verified. The maximum stress of insulator is respectively 47.01MPa, 62.72MPa and 30.85MPa, and the maximum relative displacement of the top for the equipment is 617.2mm.