Abstract
The seismic action effects of tower structures for ultra-high-voltage(UHV, upon 750KV) overhead transmission lines are much greater than those of 500KV and below, it is necessary to inspect the control load in structural design and specify the seismic design scope of tower structures for these UHV transmission lines. In this paper, the current regulations of seismic design and non-seismic design of tower structures for overhead transmission line were contrasted firstly; then, a series of typical towers including large-crossing towers and cup-towers at soft sites, on the zone of earthquake fortification intensity region of 8, were analyzed. The ratios of seismic action effects and wind load effects for characteristic value were calculated and the control load in structural design of tower structure was investigated. The results show that, although the height and the weigth of tower structures for UHV transmission lines are increasing, the control load in structural design is still the wind load on the zone of earthquake fortification intensity region of 8 and below.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.