Prompted by recent failures in earthquakes of interconnected high-voltage electrical equipment in substations and a lack of available design information, BC Hydro initiated an experimental program to address this issue. Powertech Labs, in collaboration with BC Hydro and the University of British Columbia (UBC), formulated a research plan to investigate how flexible conductors affect the seismic response of interconnected substation equipment. This paper describes the result of static tests on flexible conductors and of calculations of dynamic properties of equipment in BC Hydro substations. For a set of six interconnected configurations the natural frequencies were calculated and where possible, calibrated to the measured natural frequencies of the equipment.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.