Abstract

This paper presents the solution to the security- constrained unit commitment (SCUC) problem with a detailed representation of high voltage direct current (DC) transmission system with current source converters (CSCs). The SCUC problem is decomposed into a master problem for solving unit commitment (UC) problem and hourly transmission security check subproblems that evaluate branch flows and bus voltages of integrated AC/DC transmission systems. The solution of the transmission security check subproblem is based on a linear programming (LP) formulation that minimizes AC bus mismatches subject to AC/DC transmission constraints. The final SCUC solution prescribes an economic and secure operation and control strategy for AC/DC transmission systems and coordinates DC power transfers for enhancing the economics and the security of AC transmission systems. Numerical tests illustrate the efficiency of the proposed AC/DC transmission model.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.