Abstract
The optimum design of a high capacity double inlet pulse tube refrigerator based on second law of thermodynamics has been presented in this paper. Second law is applied to calculate the work loss in the regenerator and to optimize the cryocooler performance. To investigate the behavior of the pulse tube refrigerator, mass and energy balance equations are applied to several control volumes of the cryocooler cycle. A complete system of conservation equations is employed to solve the regenerator analytically. The proposed model reports the cooling capacity of 110 W at 80 K cold end temperature at frequency of 50 Hz, orifice conductance of 0.4 and double inlet coefficient of 0.6, with 2.4 kW net power delivered to the gas. In this case, the entropy generation in the gas phase is dominant which is contributing more than 85% of the total lost work in the regenerator. The optimum thermal efficiency of 99.1% was achieved at a proper mesh number. However, the second law efficiency is reported to have an inverse behavior at this mesh number.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.