Abstract

In the present communication, indirect and direct fired single effect vapour absorption refrigeration systems are simulated using lithium bromide-water as the working fluids. First and second Law analyses have been carried out for different operating conditions. The evaporator temperature varies from 5 to 15 °C, while the condenser temperature from 25 to 35 °C in step of 5 °C. Both coefficient of performance (COP) and exergy COP are presented for different operating conditions. Peculiar results of exergy analysis have been found for the indirect and direct fired single effect vapour absorption refrigeration systems. Exergy COP of indirect fired system is around 90% higher, while the optimum generator temperature is 19% lower than the direct fired system. Additionally, effect of preheater is also analysed on the performance of the systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.