Abstract
Surge response of the transmission tower in a three-phase transmission system is computed using s-domain nonuniform single-phase transmission line modelling. First, tower top voltage is obtained considering the tower and the ground wire by excluding the effect of the phase conductors, and then the induced voltages on the phase conductors as a result of the current flowing through the ground wire are computed using the magnetic coupling between the ground wire and the phase conductors. The first step of the analysis is the formulation of the system response in the s-domain, and the second step is the frequency to time domain conversion, which is carried out using fast inverse Laplace transform (FILT). The voltages on the phase conductors and the voltages across the tower insulators are computed, and some of the results obtained using s-domain analysis are compared with those obtaining using electromagnetic transients program (EMTP). The effect of frequency dependence of the line parameters is investigated.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.