Abstract
Background/aimsTo report the short-term safety profile and clinical outcomes of scleral fixation of intraocular lenses (IOLs) using Gore-Tex suture.MethodsRetrospective, interventional case series. 85 eyes of 84 patients undergoing ab externo...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.