Abstract

This paper presents the comparative analysis of HFC404A and its low GWP substitutes HC290, and HC1270 in saturated vapour condensation inside a 4mm ID horizontal smooth tube. The experimental tests were carried out at 30, 35, and 40°C of saturation temperatures, with refrigerant mass flux in the range 75–800kgm−2s−1 at decreasing vapour quality. A transition point from gravity-dominated and forced convection condensation was found for an equivalent Reynolds number around 10,000. The experimental heat transfer coefficients in the forced convection condensation regime were very well predicted by the Akers et al. (1959) model, whereas the Friedel (1979) correlation was able to reproduce the frictional pressure drop data in the whole experimental range. HC290 and HC1270 exhibit heat transfer coefficients higher and frictional pressure drops lower than those of HFC404A; therefore both the HC refrigerants seem to be very promising as long-term low GWP substitutes for HFC404A.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.