Abstract

The paper assesses safety of AC earthing systems in a DC traction-supply substation (TSS) by comparing the designed mesh and step voltages to the maximum tolerable voltages. Generally, IEEE 80 criteria are based on the maximum tolerable body current to prevent fibrillation of the human heart, and this current is then translated into tolerable touch and step voltages. As a result, safety assessment of AC earthing systems in a DC TSS is referred to a procedure by which the designed mesh and step voltages are computed and compared with the tolerable touch and step voltages. Computation results of AC earthing systems for the orange line at O19 TSS in Taipei rapid-transit systems are presented as an example.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.