With the application of the live working method of the zero phase potential of the working phase more and more widely, the safety of the live working operators is urgently needed for research. Considering the influence of electric shock time and frequency on the allowable current of the human body, the safe current is analyzed during live operation, and it is concluded that in the frequency range of 50~60Hz, the current below 50mA can basically guarantee that it will not die after electric shock. In the three scenarios where the insulator maintenance personnel accidentally touch the ground, the grounding wire shocks the electric shock and the charged electric shock of the tower, the human body electric shock is further analyzed. Finally, based on the CDEGS, the model of the human body contacting the grounding conductor is established. The simulation verifies the influence of the allowable current on the time and frequency of the human body withstand current under the zero potential state through the contact voltage diagram and the danger degree diagram.

Highlights

  • With the rapid development of China's power grid and the continuous improvement of power supply reliability requirements, the corresponding live working technology has made new developments and breakthroughs[1]

  • The live working of the distribution network is of great concern to the operators of live working, but the safe current is affected by many aspects during live working[2]

  • Reference [6] proved that the charging operation under bypass conditions is safe; Reference [7] introduced the method of implementing protective grounding for bypass flexible cable in integrated unpowered operation of 10kV distribution network; Three mobile power operation methods for mobile power generation vehicles, load transfer vehicles and EPS emergency power supply vehicles were introduced in [8]

Read more

Summary

Introduction

With the rapid development of China's power grid and the continuous improvement of power supply reliability requirements, the corresponding live working technology has made new developments and breakthroughs[1]. In order to analyze the safety of live operators, in recent years, the research on live working has been rapidly developed. Reference [6] proved that the charging operation under bypass conditions is safe; Reference [7] introduced the method of implementing protective grounding for bypass flexible cable in integrated unpowered operation of 10kV distribution network; Three mobile power operation methods for mobile power generation vehicles, load transfer vehicles and EPS emergency power supply vehicles were introduced in [8]. This paper considers the influence of electric shock time and frequency on the allowable current of the human body, and analyzes the safe current during live working. The simulation verifies the influence of the allowable current on the time and frequency of the human body withstand current under the zero potential state through the contact voltage diagram and the danger degree diagram

The effect of electric shock time on the allowable current of the human body
The effect of frequency on the allowable current of the human body
Insulator maintenance staff accidentally hit the ground
Ground wire electric shock
Verification of Simulation
Findings
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.