Abstract

Where the risk of accidental power-frequency energization is concerned, the safety ground has a short-circuit discharge duty determined by the configuration and parameters of the power system. Safety is thus assured by selecting a safety ground having a short-circuit safety rating which matches the duty imposed by the power system. Up to now, a similar matching for lightning currents has not been possible. This paper addresses this problem by: 1. Determining the lightning current rating of typical safety grounds. 2. Calculating the lightning current discharge duty of safety grounds in terms of the insulation level of the line and the distance from the location of the thunderstorm. The analysis shows that special precautions are needed when working on power lines of voltage classes above 360 kV.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.