Abstract
The heating affects at the end-ring connection areas of the rotor due to the harmonic current generation of a saturating unit transformer from geomagnetic induces currents (GIC) on the transmission system have been calculated from observed data and from EMTP studies sponsored by the Electric Power Research Institute. These calculations show that damage may occur during strong GIC storm activity. This damage can occur from unit transformer saturation or other transformers in the system near the generator. The possibility of damage should be monitored during strong GIC storms through the use of appropriate negative-sequence current monitoring and alarms.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.