Abstract

This paper evaluates two roof pond configurations combined with a water-to-air heat exchanger (WAHE). Test cells of 1.35 m × 1.35 m x 1.35 m with the same thermal properties, except for the roofs, are built in a hot-dry climate with mild winters. They are connected with a WAHE placed inside the roof pond's water by a pipe through which the indoor air is re-circulated. The first roof consists of a 0.35 m deep water pond covered with a floating polystyrene insulation 0.03 m thick, and a spray system located 0.5 m above it that operates at night. The second roof is covered with an aluminum plate separated by a 0.10 m air gap above a 0.25 m deep water pond. We ran multiple series and compared the results to a control cell that had a California energy code compliant insulated roof. Predictive equations are developed to dimension the WAHE system. Results demonstrate that the cells with roof ponds have better cooling performance than the code compliant control cell. The best performance is obtained in the cell with the WAHE operating continuously. In this case, the indoor temperature stayed below 24 °C even with ambient temperatures above 35 °C.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.