This paper presents commissioning details of a coordinated reactive power–voltage controller (CQVC) installed in a multimachine steam power plant (SPP). The CQVC regulates reactive power and voltage of a 1992MVA multimachine SPP. After briefly introducing basic control principles and relevant details about the CQVC's implementation, CQVC parameterization and tuning are thoroughly discussed. Once commissioned,the CQVC performance under various operating conditions is assessed. It is shown that the CQVC successfully maintains an HV busbar voltage and allocates reactive power to participating generators in accordance to their capability. Numerous CQVC responses recorded at the site are presented to demonstrate controller's performance under normal and extreme plant and network operating conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.