Abstract

This paper introduces a concept of robustness of an air distribution method, which is defined as being capable of meeting the ventilation requirements during varying operational conditions. The robustness performance may be particularly important when the system allows individual control of the supply air parameters. As a preliminary example, plenum–based (ductless) air distribution methods are studied using computational fluid dynamics. Among the four basic air distribution methods in plenum–based systems, it is found that the floor supply and ceiling return system does not always produce the conventional displacement ventilation system performance when the heat sources are not concentrated. The ceiling supply with ceiling return produces the best robustness performance over a wide range of supply velocities.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.