Abstract

Abstract: This paper describes a robust control technique for three-phase uninterruptible power supply (UPS) with output LC filter under unbalanced load conditions. The proposed control scheme consists of a combination of two robust controllers for the positive- and negative-sequence in order to provide balanced sinusoidal output voltages by eliminating the negative-sequence which caused by unbalanced loads. The gains of controller are determined by a linear matrix inequality (LMI)-based optimization so that the convergence rate to the steady state is maximized in the presence of the uncertainties in the LC filter. The uncertainties of the system are expressed as the possible ranges of inductor and capacitor values. The effectiveness of the proposed control technique has been validated and illustrated by the simulation result under unbalanced load conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.