Abstract

This study focuses on the control of instantaneous complex power of a grid-connected voltage-source inverter (VSI). In this study, a new space-vector-modulation-based direct power control approach is proposed: the robust predictive direct power control (RP-DPC). The proposed predictive control algorithm ensures that both, instantaneous real and imaginary powers, track the reference with high speed and accuracy reducing steady-state errors. In order to reduce the total harmonic distortion (THD) in the output currents, a fundamental frequency positive sequence detector is used in conjunction with a prediction grid voltage observer. Comparative simulations and experimental results of a $10$ -kW three-phase grid-connected VSI showing the steady-state and transient performance of the proposed RP-DPC are given. A low THD and balanced output currents are maintained even under severe voltage unbalance conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.