Abstract

In this paper, a novel parameter identification method for closed-loop two-input two-output (TITO) processes from step-test is proposed. Through sequential step change of set points, the coupled closed-loop TITO system is decoupled equivalently into four independent single open-loop processes with same input signal acting on the four transfer functions. Consequently, existing identification methods for single-loop process can be extended to TITO systems and the parameters of first- or second-order plus dead-time models for each transfer function can be directly obtained by using the linear regression equations derived for the decoupled identification system. The proposed method is simple for engineering application and robust in the presence of large amounts of measurement noise. Simulation examples are given to show both effectiveness and practicality of the identification method for a wide range of multivariable processes.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.