Abstract

Abstract In this paper, a simple yet robust closed-loop identification method is proposed, and an auto-tuner is then constructed by combination with a new PID tuning rule. The method can accommodate a wide range of tests such as step and relay provided that the test produces steady state responses. Using the FFT, the process frequency response is first calculated from the recorded process input and output time responses to the closed-loop test. Then the process step response is constructed using the inverse FFT. A general second-order plus dead-time model is thus obtained using our newly developed technique on robust identification of process transfer function from step responses. Simulation examples and real time test show its effectiveness.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.