Abstract
The fault current limiter (FCL) has been envisaged as a feasible solution to defend against out-of-range short-circuit currents (SCCs) in power systems. However, the existing studies mainly sited and sized FCLs under deterministic fault scenarios. Moreover, the influences of FCLs on power systems are complex including dynamic aspects, which makes it extremely difficult to configure FCLs optimally. This paper proposes a risk-based many-objective FCL configuration framework. Specifically, a data-driven Proportional Hazard Model (PHM) is developed to evaluate the nodal long-term short-circuit probability considering equipment aging, weather statistics, and surrounding conditions. The risks in terms of out-of-range SCC, abnormal voltage sag, and transient instability are formulated as the objective functions of the FCL configuration model, as well as the overall FCL investment. The time-domain dynamic response process of FCLs is considered in both the SCC limiting and the transient stability simulation process, mainly in the form of a time-varying resistance. The state-of-the-art NSGA-III is deployed to search the Pareto-optimal FCL configuration solutions of the established many-objective FCL configuration problem. The numerical results verify that the risk-based model configures FCLs more economically with a 7.5% decrease of average FCL investment compared with the deterministic model.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.