Abstract

The paper, prepared by CIGRE WG D1.03 (TF 09), presents the guidelines for risk assessment procedure on defects in GIS based on PD diagnostics. The procedure, described in detail in CIGRE Technical Brochure 525, starts with sensitive PD measurement to detect the critical defects and follows with identification of the type of the defect and its location inside the GIS. This information taken together with other essential data from laboratory measurements, manufacturer's experience, design aspects and trend analysis of the PD activity, are the base for the estimation of the criticality of the defects. Finally, the risk assessment is performed based on the estimated dielectric failure probability and failure consequences that can be different in case of on-site testing or in service activity.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.