Abstract

This paper investigates the application of a dynamic voltage restorer (DVR) to assist with the uninterrupted operation of a wind turbine driving a doubly-fed induction generator (DFIG), connected to a power network, during grid faults. In order to reduce the power rating of the DVR, the control schemes of rotor-side converter and pitch angle of the DFIG and DVR are suitably designed and coordinated. For DVR control, digital all-pass filters are used for extracting the positive-sequence component of the grid voltage. Using the positive-sequence component, the phase angles of the positive-and negative-sequence components of the grid voltage are derived. Thus, dual voltage controllers are implemented for these two sequence components in the dq synchronous reference frame. PSCAD/EMTDC simulations show the effectiveness of the proposed technique and a feasibility of reducing the cost of DVR for the fault ride-through (FRT) capability of DFIG. The validity of the proposed control scheme for the DVR has also been verified by experimental results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.