Abstract

This study experimentally determined the effects of rib spacing on heat transfer in a rotating 1:4 AR channel with a sharp-bend entrance. The leading and trailing walls used 45 deg angled ribs. The rib-height-to-hydraulic-diam ratio e/D h was 0.078. The rib-pitch-to-rib-height ratios P/e studied were P/e = 2.5, 5, and 10. Each ratio was tested at five Reynolds numbers up to 40,000. For each Reynolds number, experiments were conducted at five rotational speeds up to 400 rpm. Results showed that the sharp-bend entrance has a significant effect on the first-pass heat transfer enhancement. In the second pass, the rib spacing and rotation effect are reduced. The P/e = 10 case had the highest heat transfer enhancement, based on the total area, and the P/e = 2.5 had the highest heat transfer enhancement, based on the projected area. The current study has extended the range of the rotation number Ro and local buoyancy parameter Bo x for a ribbed 1:4 AR channel up to 0.65 and 1.5, respectively. Correlations for predicting heat transfer enhancement due to rotation in the ribbed 1:4 AR channel, based on the extended range of the rotation number and buoyancy parameter, are presented in the paper.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.