Abstract

This is the 16 slide PowerPoint presentation of Hansen and Kujak's paper. Many new lower GWP refrigerants are flammable under certain conditions. Flammability risk can be lowered by reducing the potential for forming a refrigerant/air mixture that can reach the lower flammability limit (LFL) in the event of a leak into a confined space. Product standards are setting safety factors from 4x (25% of LFL) to 1x (100% of LFL) for A2L flammable refrigerants. This large discrepancy in safety factor practices is being driven by different methodologies in understanding of refrigerant leaks from equipment. Unfortunately when a leak occurs, uniform mixing of the refrigerant with the air does not occur immediately. This can result in localized refrigerant peak concentration that exceed the LFL which requires a safety factors to be applied to account for noise factors. An additional complication is that noise factors can vary by product application.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.