Abstract
Modular multilevel converter (MMC) is one of the promising voltage source converter topologies in the field of high voltage direct current (HVDC) transmission system. Based on analysis of the existing sub-module topologies, an improved half-bridge sub-module topology based on reverse blocking IGBTs (RB-HBSM) was proposed for solving the fault ride through issues. In this paper, the fault current blocking mechanism and the electrical stress of the main power switches are studied firstly in detail. Then the fault control flow chart is presented. Feasibility of the proposed sub-module topology and the fault protection theory are verified by simulation. The proposed RB-HBSM-MMC topology is able to block the fault current without changing the original control and modulation strategies compared with the conventional MMC, thus it further reduces the complicity of industry design.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.