Abstract

Retrofitting an existing building can oftentimes be more cost-effective than building a new facility. Since buildings consume a significant amount of energy, particularly for heating and cooling, and because existing buildings comprise the largest segment of the built environment, it is important to initiate energy conservation retrofits to reduce energy consumption and the cost of heating, cooling, and lighting buildings. However, conserving energy is not the only reason for retrofitting existing buildings. The goal should be to create a high-performance building by applying an integrated, whole-building design process to the project during the planning phase that ensures that all key design objectives are met. This paper presents a real case study of the retrofitting of an existing building to achieve lower energy consumption. Indeed, most of the constructed buildings in the UAE are unsuitable for the region, which is characterized by a very harsh climate that causes massive cooling loads and energy consumption due to an appropriate selection of design parameters at the design level. In this study, a monthly computer simulation of energy consumption of an office building in Sharjah was carried out under UAE weather conditions. Several parameters, including the building orientation, heating, ventilation, and air conditioning (HVAC) system, external shading, window-to-wall ratio, and the U-values of the walls and the roof, were investigated and optimized to achieve lower energy consumption. The simulation shows that the best case is 41.7% more efficient than the real (original) case and 30.6% more than the base case. The most sensitive parameter in the retrofitting alternatives is the roof component, which affects the energy savings by 8.49%, followed by the AC system with 8.34% energy savings if well selected using the base case. Among the selected five components, a new roof structure contributed the most to the decrease in the overall energy consumption (approximately 38%). This is followed by a new HVAC system, which leads to a 37% decrease, followed by a new wall type with insulation, resulting in a 20% decrease.

Highlights

  • In the last decade, the consumption of primary energy has rapidly grown by almost 50% according to the US Energy Information Administration

  • A recent paper dealing with building retrofit and sensitivity analysis in Abu Dhabi (UAE) reported that the optimal strategies for given a case study villa are a cool roof, cool wall, seasonal energy efficiency ratio (SEER), and atrium shades, which may lead to total energy savings of 25% [27]

  • Abdullah and Alibaba reported that an integration of photovoltaics as responsive shading devices as a retrofit strategy for an energy-efficient office building would have a huge impact on energy savings

Read more

Summary

Introduction

The consumption of primary energy has rapidly grown by almost 50% according to the US Energy Information Administration. A recent paper dealing with building retrofit and sensitivity analysis in Abu Dhabi (UAE) reported that the optimal strategies for given a case study villa are a cool roof, cool wall, seasonal energy efficiency ratio (SEER), and atrium shades, which may lead to total energy savings of 25% [27]. Abdullah and Alibaba reported that an integration of photovoltaics as responsive shading devices as a retrofit strategy for an energy-efficient office building would have a huge impact on energy savings. This retrofit method has reduced total site energy consumption by 33.2% compared to the existing building performance [28]. WSuisntatirnyabhilietyat20d2i0s,p11e,rxsiFoOnRs,PbEEuRt,RoEnVItEhWe other hand, it involves a cooling energy demand increase, w4hoifc1h7 can reach up to 45% [30]

Materials and Methods
Weather Data Analysis
Energy Simulations
Alternative Selection
Retrofitting Alternatives
Glazing and Frame Types
Shading
HVAC System
Findings
Discussion

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.