Abstract

The shunt power capacitors are used as a reactive compensator while vacuum circuit breakers are used to switch shunt capacitors in power grid. To research the high over-voltage during switching off the shunt capacitors and a vacuum circuit beaker restriked, the restriking model is built with three-phase vacuum circuit breakers, considering the capacitors’ energy storage characteristic and asynchronous operating. The over-voltage is harmful to the insulation and life-circle of the equipments and even threatens power system safe and stabile operation. The variation trends of both recovery voltage between the contacts and the capacitors voltage are theoretically deduced. The model based on a 220kV substation of Guangdong grid was built and the most serious case that breakers are restriked in two phases are numbered with EMTP. Compared with theoretical results, simulation results are valid and practical.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.