Abstract

The purpose of this study was to examine whether exposure to human bioeffluents, at the levels recommended by the current ventilation standards, would cause any effects on humans. Ten subjects were exposed in a low-emission stainless-steel climate chamber for 4.25 hours. The outdoor air supply rate was set to 33 or 4 l/s per person, creating two levels of bioeffluents with carbon dioxide (CO2) at 500 or 1600 ppm. Subjective ratings were collected, cognitive performance was examined and physiological responses were monitored. The results show that exposures to human bioeffluents at ventilation rate of 4 l/s per person caused sensory discomfort of visitors, reduced pNN50 (a domain of ECG measurement), but did not produce negative effects on cognitive performance or health symptoms.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.