Abstract

Energy consumption of air-conditioning in wet and hot climates is not only for cooling but, to a large extent, for dehumidification. Taking urban agglomeration in the Pearl River Delta region as a case study, this study analysed the cooling and dehumidification loads during the past 20 years. In addition, the impacts of cooling and dehumidification loads on carbon emissions were determined. The results showed that there was large spatial heterogeneity in the variations of the cooling and dehumidification loads. The cooling design loads in 1991–2020 was increased 1.83% to 5.56% compared to those in 1971–2000, while the loads for dehumidification was decreased 0.92% to 5.5%. Carbon emissions from cooling were increased, exceeding the carbon reduction from dehumidification, which leads to a weak increase in total carbon emissions. This study revealed that air-conditioning design should fully consider climate change impact by separating cooling and dehumidification loads, increasing the cooling load to avoid insufficient air-conditioning output but reducing the dehumidification load to promote energy efficiency of the air-conditioning system and to reduce carbon emissions. More importantly, an assessment of design loads with climate change in city or small scales should be made before determining summer air-conditioning system design capacity.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.