Abstract

Resonant voltage conditions on an unenergized 765 kV line with shunt reactor compensation, excited by a nearby energized 345 kV line are examined as a function of reactor MVA rating. Results from two methods of analysis are presented. One method uses ABCD matrix analysis in a digital program and the other method uses an electrostatic argument. The electrostatic analysis predicts the number and location of the resonant peaks while the ABCD method yields the entire response curve.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.