Abstract
Owing to the high penetration of electrical energy from wind energy conversion systems (WECSs), some countries are enforcing stringent grid codes to regulate low-voltage-ride-through (LVRT) operation of WECSs. This study presents a self-tuning resonant control (RC) system which can be used for LVRT control of the grid interface in the presence of symmetrical or asymmetrical faults. Only two RCs are required to fully control the four degrees of freedom of the converter output current. Sequence component separation is achieved using a new fast-convergence delayed signal cancellation method which is also discussed in this work. The mathematical analysis and design procedure of the control system are presented. Simulation and experimental results obtained from a 3 kW prototype are discussed in this study.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.