Abstract
Simulations and high voltage field tests indicate that unacceptable and unexpected motor terminal overvoltages and waveform shapes can occur in the normal operating range with multilevel drive systems. These waveforms (if unattended) would have resulted in premature motor insulation failures. A case study of an 11 kV multilevel system is discussed. Simulations and calculations confirm the theory of resonance overvoltages. Different solution possibilities are analyzed. Further simulations and investigations are performed to determine the optimal carrier frequency. Test results confirm that the proposed modification has the desired effect; with waveforms well within limits stipulated by international standards. Simplified equations and recommendations are provided to determine suitable application solutions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.