Abstract

This paper introduces a post-disaster load restoration approach for the distribution grid, utilizing network reconfiguration (NR) and dispatching of repair crews (RCs) to significantly enhance grid resilience. We propose an RC–NR coordinated model that leverages diverse flexible resources within the active distribution network (ADN), aimed at not only enhancing the grid’s resilience level but also efficiently mending the fault lines. The model introduces fault repairing and sequential NR coupled constraints to devise an optimal resilience strategy within temporal domain cooperation, focusing on minimizing repair and penalty costs associated with the restoration process. To tackle the challenge of computational complexity, the nonlinear model is reformulated into a mixed-integer second-order cone programming model. The efficacy of the approach is validated through case studies on an IEEE 33-bus system, in which simulation results demonstrate a considerable improvement in grid resilience, achieving optimal load recovery with reduced restoration time and costs. The proposed approach outperforms traditional methods with optimal repair sequence and RC scheduling, aligned with NR efforts, and contributes to an improved system resilience level.