Abstract

To avoid saturation of a protective current transformer (CT) operating under an autoreclosing scheme, the CT size should be chosen much higher than a similar CT operating under a single-step fault clearing scheme. The main reason for this significant difference is that the residual flux (caused by the first stage of the fault) cannot be noticeably reduced during the deadtime interval of the reclosing process and, therefore, the occurrence of a subsequent fault can extremely saturate the CT. In this paper, a low-cost, low-power electronic device is developed and introduced to demagnetize the CT under the reclosing deadtime interval. It will be shown that by using this device, the required size of the CT is reduced by about 40%. To develop this device, an existing flux-based demagnetization technique is improved to operate faster and more efficient. The performance of this technique is independent of the CT characteristic parameters and provides promising results despite its simplicity. The proposed device can be employed to de-rate the new CTs to be installed in the system and/or to compensate the existing inservice CTs. Comprehensive computer simulations and laboratory experiments are employed to validate the reliability and effectiveness of the proposed compensation method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.