Abstract
Abstract Converter transformers are an interface point of HVDC frameworks and are basic hardware from activity and reliability view point. Converter transformers are turned off intentionally under planned support and un-deliberately during fault conditions. Random energization of HVDC Converter transformer delivers high inrush currents due to core saturation asymmetries and endanger equipment health. In this paper, charging approach has been proposed. By utilizing point on wave exchanging for moderation of charging drifters during charging of 888 MVA 400/325 kV Converter Transformer of ±800 kV HVDC Sub-station. The proposed procedure has been applied on HVAC electrical Circuit Breaker furnished with Pre-Insertion Resistor considering diverse degree of residual flux. Performance of proposed philosophy has been affirmed by field tests and reproduction in PSCAD programming package and is found very viable. Near investigation is done in this paper and shows that with the use of proposed system, the switching transient during stimulation and field tests of coupled three phase converter transformers is decreased to worthy level.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Emerging Electric Power Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.