Abstract

ABSTRACTResidential inter-zonal (e.g., between rooms) ventilation is comprised of fresh air infiltration in and exfiltration out of the whole house plus the “fresh” air that is entering (and exiting) the room of interest from other rooms or areas within the house. Clearly, the inter-zone ventilation rate in any room of interest will be greater than the infiltration/exfiltration ventilation rate of outdoor air for the whole house. The purpose of this study is to determine how much greater the inter-zonal ventilation rate is in typical U.S. residences compared to the whole house ventilation rate from outdoor air. The data for this statistical analysis came from HouseDB, a 1995 EPA database of residential ventilation rates. Analytical results indicate that a lognormal distribution provides the best fit to the data. Lognormal probability distribution functions (PDFs) are provided for various inter-zonal ventilation rates for comparison to the PDF for the whole house ventilation rates. All ventilation rates are expressed as air change rates per hour (ACH). These PDFs can be used as inputs to exposure models. This analysis suggests that if one were performing a deterministic analysis for unknown housing stocks in the U.S., a default mean and median ACH values of 0.4/hr and 0.3/hr, respectively, for whole house ventilation would be appropriate; and 0.7/hr and 0.6/hr, respectively, for inter-zonal ventilation.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call