Abstract

Based on the dynamic mathematical model of three-phase grid-connected inverter, two kinds of control strategies are compared, one is double closed loop control based on grid voltage orientation theory, the other is direct power control. According to the mathematical model of two-phase rotating coordinates of the inverter, in double closed loop control theory, the purpose of control of the inverter by decoupling control and PI control is achieved. From the point of energy on direct power control system, the active, inactive power of output AC of inverter are calculated ,and suitable space voltage vector was selected after comparing with the given values to realize the direct control of the power set point. The basic theory of two control strategies and implementation method are included, and the simulation model was established based on MATLAB/Simulink. And their simulation results, characteristics of two kinds of control methods were compared through simulation data analysis. On the basic of results, the direct power control is better than the double closed loop control.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.