Abstract

In the initial period of power system restoration, charging the transformer without load will result in sympathetic inrush current appearing in its adjacent transformer. The sympathetic inrush current will appear as a result of the saturation‥ In view of fundamental representations of flux linkage, with the help of the integral model of sympathetic inrush of two shunt-wound transforms, the paper derives a formula that the sympathetic inrush current value is decided by the integral value of public bus voltage in a period. From the formula, this paper get the generation reason of sympathetic inrush current that public bus voltage in two shunt-wound transforms depresses suddenly so that linkage of neighboring running transformer changes. Then analyzes the influence of system resistance on sympathetic inrush current. This analysis provides a sound theoretical basis for a complete understanding of the phenomenon.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.