Abstract
In order to achieve high-accuracy self-calibration and traceability of electromagnetic standard voltage transformers, a measurement method that can be used for voltage ratio standard error voltage coefficients is proposed. Using two auxiliary standard voltage transformers, the error variation of the voltage transformer under different voltages can be obtained through three-step measurement. Compared with the traditional error voltage coefficient measurement method and international comparison, the feasibility of the method and the rationality of the uncertainty evaluation of the measurement results are verified. The self-calibration ratio difference measurement uncertainty of the 110 kV standard voltage transformer is better than 5 × 10−6, and the angular difference measurement uncertainty is better than 5 µrad. The method can be used to trace the source of standard devices up to 1000 kV power frequency voltage ratio, which have characteristics such as high accuracy and good stability.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.