Abstract

An architecture that has obtained a three-star green building design identity certificate was taken as an example in my thesis. We analyzed the data of ground source heat pump, photovoltaic power generation and energy consumption monitoring system in this project. Based On actual usage of the three green passive technologies, we find some problems and get some conclusion. System efficiency of ground source heat pump meet requirements of the renewable energy construction application engineering evaluation standard GB-T 50801-2013,and at the same time satisfy the requirements of the green building evaluation standard GB 50378-2006. Photovoltaic power generates 350400 kWh per year and reduces carbon dioxide emissions by 346.9 tons. But it is lower than the theoretical value by 31%.The data Energy consumption monitoring platform is higher than the electricity supply bureau by 12.68% .The data of Sub-item measured close to the calculated value. The error is less than by 3%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.