Abstract

It is necessary to construct a physical reproduction environment that conforms to the actual working conditions of single-phase grounding faults in 10 kV distribution networks, to effectively verify the single-phase grounding fault disposal capability of distribution automation equipment. In this article, a physical reproduction method of a single-phase ground fault in distribution networks based on digital mirroring is proposed. A digitized mirror model of a single-phase ground fault of a 10 kV distribution network is constructed. The system architecture for equivalent physical reproduction of single-phase grounding fault characterization is designed. Then the solutions to the critical technical problems in the realization are proposed. The reproduced single-phase ground fault signal was applied in the functional verification work of the first and second fusion distribution equipment. The experimental results show that the single-phase grounding fault in the 10 kV distribution network reproduced by this method comprehensively verifies the correct rate of the equipment for the single-phase ground fault disposal as well as the ability to prevent false action. Moreover, the reasons for the failure of the equipment s single-phase grounding fault disposal function were discovered.