Abstract
Based on the spectral temperature measurement, the arc radiation image is obtained by CCD camera in this paper, which is processed with digitalized treatment. Finally the three colors RGB of the digital matrix was obtained. The RGB value can be analyzed by the method of colorimetric temperature measurement. Comparing the data with the temperature of the arc in some given point, the corresponding relation between the temperature and gray level can be established. The image histogram of the arc is analyzed in our work and the variation of isotherm and arc core can be detected by defining the various temperature boundaries through high frequency signal components comprising edges and outlines of arc images. Meanwhile, the areas of different temperatures are defined by the Pseudo-color Technique. Eventually, a dynamic 2-D thermal field can be obtained by the images of arc, which is a feasible method for the measurement of the temperature of the arc in the switch apparatus.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.